|
INTRODUCTION
A thermostatic expansion valve ( TXV) is precision device used
to meter the flow of liquid refrigerant entering the evaporator at a
rate that matches the amount of refrigerant being boiled off in the
evaporator, This is it's main purpose but like all the other metering
devices it also provides a pressure drop in the system, separating the
high pressure side of the system from the low pressure side. thus
allowing low pressure refrigerant to absorb heat onto it's self.
OPERATION
The valve it self has 3 forces that act upon each other to accomplish
this task. They are
 |
Bulb Pressure P1 |
 |
Evaporator Pressure P2 |
 |
Spring Pressure P3 |

As you can see from figure 1 there are 2 closing forces P2
& P3 and one opening force P1. The valve in this figure is in
equilibrium, P1 = P2+P3. If the evaporator pressure was to
increase while the bulb pressure stayed that same the valve would close.
P2 + P3 would be greater than P1. Now if the bulb pressure was to
increase to the larger amount, the valve would open . P1 is greater than
P2+P3.

Photo Property of the respected owner
In this example we will be discussing the operation of the most basic
type of TXV, the single outlet style. We will also be assuming there is
no pressure drop in the evaporator as well as no requirement for super
heat.
As the load across our evaporator increases the available refrigerant
will boil off more rapidly, if it is completely evaporated prior
to exiting the evaporator , the vapor it self will continue to absorb
heat . This heat is referred to as super heat, Superheat is heat added
to a substance above it's saturation temperature. The bulb will sense
this increase in temperature exiting the evaporator and increase the
pressure on P1. P1 now being greater than P2+P3 will allow the valve to
open allowing more refrigerant to enter the evaporator. Now that more
refrigerant is being introduced into the evaporator there is more
availability to absorb heat, if there is insufficient heat to boil off
all the refrigerant prior to it exiting the evaporator the temperature
at the sensing bulb will decrease reducing the pressure at P1 and
causing the valve to close. P1 is less than P2+ P3.
SUPERHEAT SETTING
As previously mentioned super heat is heat added to a substance above
its saturation temperature. As refrigeration mechanic's we must be
concerned with the amount of super heat we have in a system. To little
and we may have liquid refrigerant entering our compressor washing out
the oil and at worst case, causing hydraulic pressure thus breaking
mechanical parts. To much and we are wasting valuable evaporator space
and possibly causing compressor overheating problems. From the factory
TXV's come pre calibrated at a static superheat setting 6oF. Static
superheat is the amount of superheat required to get the pin to begin
travel, any increase of superheat over this point is referred to a
gradient. The manufactures often calibrate for 4o to 6oF of gradient
superheat, The combination of the 2 mean that at 10o to
12oF total
superheat the valve will be opened to it's full rated capacity.
Please note that this superheat setting is set at the exiting of the
evaporator and not at the compressor so to see a 15oF superheat reading
at the compressor is normal.
EXTERNALLY EQUALIZED
Externally equalized TXV's must be used when the pressure drop in the
evaporator exceeds
 |
3oF for Air Conditioning |
 |
2oF for Refrigeration |
 |
1oF for Low Temp applications |

Looking at figure 3 you will notice that we are leaving our TXV with
a refrigerant pressure of 69 PSIG @ 40oF this is saturation for R22. As
the refrigerant passes through the evaporator it experiences a pressure
drop of 10 PSIG. Now with a refrigerant pressure of 59 PSIG our
saturation temperature is 33oF, once our refrigerant has completely
evaporated we will start to add super heat to it and the condition
leaving the evaporator will be a low temperature, low pressure superheated
vapor 59 PSIG @ 50F . At 59 PSIG our saturation temperature
is 33oF and leaving the evaporator the refrigerant temp is 50F this means
there is 17oF superheat, Saturation temp - leaving temp = superheat.
since our superheat setting is 10oF the 85 PSIG bulb pressure is greater
than the evaporator pressure at the external equalized port and the
spring pressure (85 > 59+16). there fore the valve will open and allow
more refrigerant into the evaporator. If in this example we did not use
a externally equalized TXV our valve would be at equilibrium and
not allow any more refrigerant to enter (85=69+16).
Valve Hunting
One of the major problems with single ported valves is that they are susceptible
to valve hunting. Valve hunting is defined as the alternate overfeeding
and starving of refrigerant flow to the evaporator. This can be noticed
buy the constant movement you may see in your refrigerant gauges.
Hunting can be reduced buy either relocating the sensing bulb to a
better location or by purchasing a valve designed for reduced hunting.
Balanced Port Valves
Balanced port valves are designed for systems that experience fluctuating
pressures. On conventional TXV's when the pressure drop across them
changes so does the amount of superheat, Potentially you could have
either flooding or overheating of the compressor due to this reason. The
balanced port cancels this effect allowing proper superheat to be
maintained.
Double Ported Balanced Port valves
When dealing with systems that have light load conditions, double
ported valves should be used these valves have 2 ports for varying capacities
and can run down to 15% of their rated tonnage.
Todd Legere
Copyright © 2000 HVAC Mechanic.com . All rights reserved.
Revised: September 22, 2002
.
|